The difference between cooling tower tonnage and water tonnage
Cold ton CRT and water ton T/H are two different concepts, representing different measurements in the cooling tower industry. The specific analysis is as follows:
definition
Cold ton CRT: The cooling tower cools the process water temperature of 780 l/h from 37 ° C to 32 ° C at a wet bulb temperature of 27 ° C.
Water ton: According to the national standard, the cooling tower is required to cool 1000 l/h of process water from 37 degrees Celsius to 32 degrees Celsius at a wet bulb temperature of 28 degrees Celsius.
There are many suppliers in the market who use CRT to represent cooling tower capacity, but there is a suspicion of using small to large specifications. The selection party should pay special attention.